ANALISIS SISTEM PEMBUMIAN TOWER SALURAN TRANSMISI DARI GARDU INDUK KAPAL – GARDU INDUK GIANYAR
Main Article Content
Abstract
This study aims to improve the earthing value of transmission lines which have an earth
value less than the standard value off SPLN No 121: 1996, namely 10 and recommend an
earthing system that meets the standards. Theemethodduseddissa descriptive method by
calculating the value of the earthing system by following the SPLN standard No. 121: 1996. This
analysis consists of several stages, namely a site survey, measuring soil resistance (R) to
calculate the value of soil resistivity (?) then calculating the value of grounding resistance with 5
types of grounding systems to achieve grounding resistance 10 , namely one electrode
grounding system, 2 electrode grounding system planted vertically S > L, 2 electrode earthing
system planted vertically S < L, plate earthing system, and a grid-rod earthing system. The
results of the research are for paddy fields using a vertical one-electrode earthing system, the
value is 7.32 ? with a manufacturing cost of Rp. 857,000, on farmland with a vertical oneelectrode
earthing system, the value is 8.36 ? with a manufacturing cost of Rp. 1,363,000, and
on clay soil with a vertical one-electrode earthing system, the result is 7.98 ? with a
manufacturing cost of Rp. 857,000.