Simulasi Penggunaan Komponen Smart Building untuk Meningkatkan IKE di Gedung Rektorat Universitas Udayana
Abstract
One of the important aspects in energy management is energy audit activities. he benefits of an energy audit include recommendations for actions to be taken to improve energy efficiency, reduce costs and save money on energy bills. This study aims to obtain information on the efficiency of the use of electrical energy in the rectorate building of Udayana University and how big the potential for saving electrical energy is through testing energy-saving equipment. The results of the measurement, observation and data collection of the load at the Udayana University rectorate, the total power and electrical energy consumption of the Udayana University Rectorate building are 120.12 kW and 15521.02 kWh, respectively. The biggest need for electricity supply is air conditioning, which is 61.5 kW with energy consumption of 62%. In general, the Rectorate building of Udayana University has an IKE value of 49.43 kWh/m2/year. The IKE value for the AC/non-AC building category is 4.12 kWh/m2/month (very efficient). Meanwhile, in terms of IKE per room, there is still a value below the efficient category because electrical equipment is still / left on when working hours are over, especially lights and air conditioners. The application of Smart Building equipment with the aim of efficient use of electrical energy shows a decrease in lighting electrical energy consumption by 161.25 kWh (31%) while for air conditioning by 143.86 kWh (11%).
Downloads
References
[2] D.S. Pasisarha, “Evaluasi IKE Listrik Melalui Audit Energi Awal Eergi Listrik di Kampus Polines,”. JTET, 1, 1 – 7, 2012.
[3] D. Despa, G.F. Nama, T. Septiana, M.B. Saputra, “Audit Energi Listrik Berbasis Hasil Pengukuran dan Monitoring Besaran Listrik Pada Gedung A Fakultas Teknik Unila,” Electrician-Jurnal Rekayasa dan Teknologi Elektro, Vol. 15, No. 1, 2021.
[4] K.A.N. Saputra, I.B.G. Manuaba, R.S. Hartati, “Upaya konservasi Energi Listrik Pada Kawasan Pusat Pemerintahan Kabupaten Badung Mangupraja Mandala,” Majalah Ilmiah Teknik Elektro, Vol. 18, No. 1, Pp. 41-46, 2019.
[5] I M.S. Dwikarta, N.S. Sastra, D.M. Wiharta, “Kinerja Jaringan Sensor Nirkabel untuk Model Smart building,” Majalah Ilmiah Teknologi Elektro, Vol.20, No.2, Pp 211-222, 2021.
[6] S. P Anggara, A. A. N. Amrita, D. C. Khrisne, 2018. Rancang Bangun Alat Kontrol dan Monitoring Konsumsi Listrik Lampu Penerangan Jalan Umum Berbasis Mikrokontroler ATMega 2560. Majalah Ilmiah Teknologi Elektro, Vol. 17, No. 3, Pp 427-432, 2018.
[7] N. C. Utomo, R. Primananda, R. A. Siregar. Analisis Pemakaian Energi Pada Sensor Node Dengan Protokol Komunikasi Zigbee Menggunakan Solar Cell. Jurnal Pengembangan Teknologi Informasi dan Ilmu Komputer, Vol. 2, No. 9, hlm. 3006-3012, September 2018.
[8] W. Wiyardani, H. Mistialustina. Aplikasi Penampil Data Hasil Monitoring Suhu dan Kelembaban Ruangan pada Wireless Sensor Network. Jurnal Infotronik Volume 5 No. 1, Pp 22-36, 2020.
[9] H.N. Pratama, R.S. Hartati, I.N.S. Kumara, “Studi Pengelolaan Energi Listrik Di Perusahaan Pengolahan Daging PT. SOEJASCH BALI,” Teknologi Elektro, Vol.16, No. 02, Pp 31-36, 2017.
[10] Samsuddin, Suriadi, Y. Away, “Audit dan Optimasi Energi Listrik Pada Bangunan Kampus Menggunakan Metode Algoritma Genetika,” Jurnal Nasional Komputasi dan Teknologi Informasi, Vol. 2, No. 1, 2019.
[11] Pemerintah Republik Indonesia, “Peraturan Pemerintah Republik Indonesia Nomor 70 tahun 2009 tentang Konservasi Energi,” Jakarta : Sekretariat Negara RI. Kepala Biro Peraturan Perundang-Undangan Bidang Perekonomian dan Industri, 2009.
[12] Kementerian Energi dan Sumber Daya Mineral Republik Indonesia, “Permen ESDM No. 14 Tahun 2012 Tentang Manajemen Energi,” Jakarta : Biro Hukum dan Humas ESDM RI, 2012.
[13] A.W. Biantoro, D.S. Permana, “Analisa Audit Energi Untuk Pencapaian Efisiensi Energi di Gedung AB,” Kabupaten Tanggerang, Banten: Jurnal Teknik Mesin (JTM), Vol. 06, 2017.
[14] J.C. Teruna, “Audit Energi Awal Melalui Perhitungan Intensitas Knsumsi Energi (IKE) Listrik (Studi Kasus Pada Gedung Politeknik Muara Teweh,” Jurnal Elektrika Borneo, Vol 5, No. 2, Pp 27-30, 2019.
[15] Synergy Solusi, (2020) ‘Bantu Capai Program Efisiensi Dengan Audit Energi,’ [Online]. https://www.synergysolusi.com/berita/berita-terbaru/bantu-capai-program-efisiensi-dengan-audit-energi.html
[16] A. Hadi, Z. Abidin, W.M. Faizal, “Analisa Proses Audit Energi Listrik di Gedung D Politeknik Negeri Bengkalis,” Prosiding Seminar Nasional Teknik Elektro, Vol. 5, 2020.
[17] S.K. Azifah, I. Waspada, “Rancang Bangun Smart Building Dalam Memantau dan Mengendalikan Lampu Secara Realtime Berbasis Websocket,” Jurnal Infokam, No. II, 2017.
[18] I N. Yudiyana, I.N.S. Kumara, R.S. Hartati, “Studi Manajemen Energi Listrik di RSUD Kabupaten Klungkung,” Majalah Ilmiah Teknologi Elektro, Vol.18, No. 02, Pp 203-210, 2019.
[19] C.Y. Rachmat, I.N.S. Kumara, I.A.D. Giriantari, “Studi Manajemen Energi di Rumah Sakit Prima Medika Denpasar,” Majalah Ilmiah Teknologi Elektro, Vol.18, No. 1, Pp 23-34, 2019.
[20] I.D.A.P.W. Artati, “Studi Terhadap Manajemen Energi di Rumah Sakit Umum Pusat Sanglah Denpasar. Denpasar,” M.T. Thesis, Universitas Udayana, Badung, Bali, 2016.
This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.
This work is licensed under a Creative Commons Attribution 4.0 International License