Kutampi Diesel Power Plant that supplies the Lembongan Island electrical system has a reliability value index that has not met the standard with SAIDI 95.85 hours / customer / year and SAIFI 76 times / customer / year while the WCS standard for SAIDI is 2.5 hours / customer / year and SAIFI is 3 times / customers / year. Reliability value can be improved one of them by adding recloser. The addition of the recloser should pay attention to the area of frequent interference, the percentage of load and impedance of the electricity system. The VEGA method was used to determine the optimal recloser location by minimizing the SAIDI and SAIFI values. The result of the optimization method using VEGA shows optimal recloser location in the group 5 with the highest fitness 8,8396 with SAIDI 0,0070 hour / customer / year and SAIFI 0,0061 times / customer / year with program running time ± 3,6 minutes. These values indicate the VEGA method is more accurate than the fuzzy and genetic algorithm combination method but requires a longer running time.


 

Downloads

Download data is not yet available.

References

[1] Hartati, R. S., Sukerayasa, I. W. “Penerapan Metode Pendekatan Teknik untuk Meningkatkan Keandalan Sistem Distribusi”. Teknologi Elektro, Vol.9, No.1, (Januari-Juni) : 50-53. 2010.
[2] Putra, I. M. Y. L. “Optimasi Penempatan Recloser untuk Memperbaiki Keandalan Sistem Distribusi pada Penyulang Lembongan Menggunakan Metode Kombinasi Logika Fuzzy dengan Algoritma Genetika”. Teknologi Elektro dan Komputer, Vol. 15, No.1, (Januari-Juni) : 2016
[3] Amrita, A.A.N. 2007. Penentuan Posisi dan Kapasitas Optimal Bank Kapasitor pada Sistem Distribusi Menggunakan Virus Evolutionary Genetic Algorithm (VEGA). Surabaya: Institut Teknologi Sepuluh November Surabaya.
[4] PT. PLN (Persero). 1997. PBO-SSO. Jakarta: PT.PLN (Persero) Pusat Pendidikan dan Pelatihan.
[5] NN. 2017. OVR ANSI / IEC MV outdoor vacuum reclosers. http://new.abb.com/medium-voltage/apparatus/reclosers/ansi-iec-single-and-three-phase-recloser-ovr. Diakses tanggal 15 April 2017.
[6] Marsudi, D. 2006. Operasi Sistem Tenaga Listrik. Yogyakarta: Graha Ilmu
[7] Brown.R. 2009. Electric Power Distribution Reliability, Second Edition, New York, CRC Press Tylor & Francis Group.
[8] PT. PLN (Persero). 1985. Keandalan Pada Sistem Distribusi 20 kV dan 6 kV. Jakarta: SPLN No.59 : 1985.
[9] Sutojo, dkk. 2010. Kecerdasan Buatan. Semarang: Andi.
[10] Zukhri. Z. 2013. Algoritma Genetika Metode Komputasi Evolusioner untuk Menyelesaikan Masalah Optimasi, Yogyakarta, Andi.
[11] Suyanto. 2005. Algoritma Genetika dalam MATLAB. Yogyakarta, Andi
[12] Arigandi, G. P. B., Hartati, R. S., Weking, A. I. “Analisa Keandalan Sistem Distribusi Penyulang Kampus dengan Menggunakan Penggabungan Metode Section Tecknique Dan Ria”. Teknologi Elektro, Vol. 14, No.2, (Juli-Desember) : 1-5. 2015.
Published
2018-05-23
How to Cite
IRAWAN, Novadianto Yudha; AMRITA, Anak Agung Ngurah; SETIAWAN, Widyadi. Optimasi Penempatan Recloser untuk Meningkatkan Keandalan Menggunakan Metode Virus Evolutionary Genetic Algorithm (VEGA). Majalah Ilmiah Teknologi Elektro, [S.l.], v. 17, n. 2, p. 177-184, may 2018. ISSN 2503-2372. Available at: <https://ojs.unud.ac.id/index.php/mite/article/view/32751>. Date accessed: 04 dec. 2024. doi: https://doi.org/10.24843/MITE.2018.v17i02.P03.