ANALISIS PENGARUH INTERKONEKSI DISTRIBUTED GENERATION (PLTSA SUWUNG) TERHADAP RUGI-RUGI DAYA DAN KEANDALAN PADA PENYULANG SERANGAN
Abstract
The distributed generation technology or in this
case abbreviated DG is a kind of power plants with small
scale which prioritizes the utilization of renewable energy
resources such as wind, water, solar, geothermal, ocean waves
(Wave Energy), ocean currents (Ocean Current Energy),
biomass, and biogass to produce the electrical energy with
range of power generation between 1 kW-10 MW. One of the
DG in Bali and still in operation is the garbage power plant
which located in Suwung, South Denpasar. An analysis has
been done using load flow analysis and reliability assessment
to determine the effect of DG interconnection against the
power losses and the level of reliability on the Serangan
feeder. Based on the research that has been done, DG
intercon-nection on the Serangan feeder decrease the power
losses and increase the reliability and it can visible from the
acquisition of SAIFI and SAIDI index which decreased. The
best location of DG interconnection to get low of the power
losses and the high level of reliability is at 97% from the total
length of the feeder. At that location the power losses is
decrease as big as 4.5 kW or 11.25% of the total power lossess
without the DG interconnection and decrease of the SAIFI and
SAIDI index respectively to 0.1 failure/customers/year and
1.4150 hour/ customer/year
Downloads
Keywords
This work is licensed under a Creative Commons Attribution 4.0 International License