Coral Rock Thickness Grounding System Switchyard Substation In Clay

  • IGN Janardana udayana university
  • I Wayan Arta Wijaya

Abstract

The grounding of the equipment at the substation switchyard location is given a layer of coral about 10 cm above the ground surface to reduce the tension difference on the ground surface and increase the resistance of the human feet around it. The purpose of this study was to determine the thickness of the coral in the grounding system of switchyard equipment in clay. This research analysis method calculates the results of the coral thickness value to achieve the step voltage and touch voltage values ??according to the IEEE Std 80-2013 standard so that it can provide safety for the equipment and people around it. The results of this study are that the thickness of the coral 0.15 meters produces a touch voltage value = 150.3675 volts (dry conditions) and 148.63 volts (wet conditions) and the step voltage is the smallest and best with a value = 206.83 volts ( dry conditions) and 163.98 volts (wet conditions when compared to the thickness of the coral 0.08 meters to 0.14 meters, so it is concluded that the thickness of the coral is best to be installed at the substation on clay of 0.15 meters is good when the soil and coral are wet or dry, so that it has an impact on the function of the grounding system to function properly and safely for equipment and humans.


 


Keywords— Coral, Earthing, Clay.

Downloads

Download data is not yet available.

References

[1] Agung, J. 2015. Perancangan Sistem Pengetanahan Peralatan di Gardu Induk PLTU IPP (Independent Power Producer) Kaltim 3. Malang : Universitas Brawijaya.
[2] Suciawan, IPN. Janardana, IGN, Wijaya, IWA. 2021. Pengaruh Ketebalan Batu Koral Pada Tanah Lempung Dan Tanah Berpasir Terhadap Tegangan Langkah Dan tegangan Sentuh. Jurnal SPEKTRUM; Volume 8 No. 1 Maret 2021.
[3] Mahadewi, KM., Janardana, IGN., Wijaya, IWA., 2019. Analisis Tegangan Langkah dan tegangan Sentuh Serta Perencanaan Sistem Pembumian Pada Pembangunan Substation VVIP. Di Bandara Internasional I Gusti Ngurah Rai Bali. Journal SPEKTRUM Volume 6, No. 1 Maret 2019. Jimbaran : Program Studi Teknik Elektro Universitas Udayana.
[4] Suartika M. 2017. Sistem Pembumian (Grounding) Dua Batang Sistem Pengaman Tenaga Listrik. Bali: Universitas Udayana Bali.
[5] ] IEEE Standard 80 - 2000. (2013). Guide For Safety In Ac Substation Grounding. New York
[6] Tanjung, A. 2015. Analisis Sistem Pentanahan Transformator Distribusi di Universitas Lancang Kuning Pekanbaru. ISSN: 1693-2390 Jurnal Sains, Teknologi dan Industri, Volume 12 (2). Pekanbaru: Jurusan Teknik Elektro Fakultas Teknik Universitas Lancang Kuning.
[7] Kamal, J, Abduh, S. 2018. Perancangan Sistem Pentanahan Gas Insulated Switchgear 150 kV Pulogadung dengan Finite Element Method. JETri, Volume 15 (2). Jakarta: Jurusan Teknik Elektro Fakultas Teknologi Industri Universitas Trisakti.
[8] Latif, A. 2016. Probabilitas Tegangan Sentuh dan Tegangan Langkah di Lokasi Rencana Gardu Induk 500 kV Antosari. Bali: Universitas Udayana.
Published
2023-07-26
How to Cite
JANARDANA, IGN; WIJAYA, I Wayan Arta. Coral Rock Thickness Grounding System Switchyard Substation In Clay. Journal of Electrical, Electronics and Informatics, [S.l.], v. 7, n. 1, p. 23-27, july 2023. ISSN 2622-0393. Available at: <https://ojs.unud.ac.id/index.php/jeei/article/view/98094>. Date accessed: 12 dec. 2024.