Effect Of Value Of Resistance Announcement To Thd In Electrical System Faculty Of Engineering University Udayana Denpasar

  • I. G. N. Janardana Electrical Engineering Department, Faculty of Engineering, Udayana University, Bukit Jimbaran, Indonesia
  • I W Arta Wijaya Electrical Engineering Department, Faculty of Engineering, Udayana University, Bukit Jimbaran, Indonesian
  • I. N. Karnata Mataram Civil Engineering Department, Faculty of Engineering, Udayana University, Bukit Jimbaran, Indonesia

Abstract

AC (Air Conditioner), TV, lamp, LCD and others are categorized as nonlinear load generating harmonics. The high content of harmonics has a negative impact on the quality of electrical power. The result of measurement of THD (Total Harmonic Distortion) current at 9 ohm ground resistance value at phase R = 9,8%, phase S = 11,0%, phase T = 7,5% exceed from standard value IEEE 519 Year 2014 equal to ? 5 , 0%, THD measurement of phase voltage R = 1.4%, phase S = 1.2%, phase T = 1.3%, meet the maximum THDv standard of ? 5%. To overcome this problem, it was observed the effect of the value of ground resistance to THDi and THDv on the electrical system of the College of Engineering Faculty of Denpasar. This method of analysis with ETAP software simulation. With grounding system ? 3 ohm only effect on current THD only with decreasing value of THDi become: phasa R = 4,2%, phase S = 5% and phase T = 4,3%, meaning with grounding system ? 3 ohm THD current fulfill IEEE 519 - 2014 standard <5%. while THD voltage has no effect (THD value of fixed voltage). Several studies have suggested that THD repair can be done by filter installation. However in this study the installation of grounding system ? 3 ohms can reduce the value of current THD.

Downloads

Download data is not yet available.

References

[1] Wahyu Adi Merta, IW., dkk. 2016. Analisis Pemasangan Filter Pasif Untuk Menanggulangi Distorsi Harmonisa Terhadap Beban Non Linier di PT. Wisesa Group. E -Journal Spektrum.
[2] Janardana, IGN. 2016. Sistem Pembumian Tipe Rod Sebagai Pengaman Peralatan Ruang Studio Teknik Arsitektur Gedung B Fakultas Teknik Universitas Udayana Jalan PB. Sudirman Denpasar. Denpasar : PS Teknik Elektro Unud –Perpustakaan Universitas Udayana.
[3] Janardana, IGN., dkk. 2016. Analisis Sistem Pembumian Sebagai Pengaman Peralatan Gedung Fakultas Teknik Universitas Udayana Denpasar. Laporan Penelitian : Fakultas Teknik Universitas Udayana.
[4] Hutaruk.TS.1987, Pengetanahan Netral dengan sistem Tenaga dan Pengetanahan Peralatan. Jakarta : Erlangga.
[5] Mahendra, IGMO. 2004. Study Kasus Kegagalan Proteksi Dari Bahaya Petir DI Hotel Sanur Beach Bali. Tugas Akhir. Denpasar : Teknik Elektro.
[6] Sutikno, dkk. 1997. External & Internal Grounding. Bandung : DIVLAT PT. Telkom.
[7] Dugan, RC., dkk. 2012. Electrical Power Systems Quality, Third Edition. McGraw Hill Professional.
[8] Susiono. 1999. Penentuan Lokasi Lokasi Filter Harmonik Optimum Pada Sistem Distribusi Daya Listrik.Surabaya : Program Studi Teknik Elektro Institut Teknologi Sepuluh Nopember.
[9] Sunanda. 2012. Aplikasi Filter Pasif Sebagai Pereduksi Harmonik Pada Inverter Tiga Fase.
[10] IEEE Std 519™-2014 Revision of IEEE Std 519-1992
[11] Suryajaya, A. 2011. Pengaruh Total Harmonic Distortion (THD) Pada Suatu Sistem.Semarang : Program Studi Teknik Elektro Jurusan Teknologi Industri Universitas Katolik Soegijapranata.
Published
2018-02-10
How to Cite
JANARDANA, I. G. N.; ARTA WIJAYA, I W; KARNATA MATARAM, I. N.. Effect Of Value Of Resistance Announcement To Thd In Electrical System Faculty Of Engineering University Udayana Denpasar. Journal of Electrical, Electronics and Informatics, [S.l.], v. 2, n. 1, p. 21-24, feb. 2018. ISSN 2622-0393. Available at: <https://ojs.unud.ac.id/index.php/jeei/article/view/40658>. Date accessed: 14 nov. 2024. doi: https://doi.org/10.24843/JEEI.2018.v02.i01.p05.