RUGI – RUGI DAYA AKIBAT PENGARUH KETIDAK SEIMBANGAN BEBAN TERHADAP ARUS NETRAL PADA EFEKTIFITAS PENGGUNAAN DAYA TERPASANG

Main Article Content

I Gede Budiyasa I Wayan Artha Wijaya Tjok Gede Indra Partha

Abstract

The increasing need for electrical power with a stable and continuous distribution of
electricity networks is an absolute requirement in meeting the needs of electrical energy. The
load imbalance between each phase (phase R, phase S, and phase T) which flows a net current
in the transformer, because of the transformer tolerance set by PLN, which is 20% of the power
capacity of the transformer In Abiansemal feeders there is a load imbalance of more than 20 %
then in this study the load balancing is carried out in the LVMDV panel on three-phase
customers, which has an impact on the load imbalance between each phase (phase R, phase
S, and phase T) which causes a neutral current and causes losses (losses). Based on this
problem, balancing must be done by measuring first. From the measurement results in the
LVMDP panel on three-phase customers and data obtained from the results of measurement of
load imbalance during the day is 29.9% and 26.6 % and the load imbalance at night is 62.6%
and 31%, as shown in Table 4.5, it can be seen that the bush on the large current neutral IN
that flows in the transformer neutral conductor, the greater the loss in the neutral conductor
(PN).

Downloads

Download data is not yet available.

Article Details

How to Cite
BUDIYASA, I Gede; ARTHA WIJAYA, I Wayan; INDRA PARTHA, Tjok Gede. RUGI – RUGI DAYA AKIBAT PENGARUH KETIDAK SEIMBANGAN BEBAN TERHADAP ARUS NETRAL PADA EFEKTIFITAS PENGGUNAAN DAYA TERPASANG. Jurnal SPEKTRUM, [S.l.], v. 8, n. 1, p. 260-267, mar. 2021. ISSN 2684-9186. Available at: <https://ojs.unud.ac.id/index.php/spektrum/article/view/71679>. Date accessed: 21 nov. 2024. doi: https://doi.org/10.24843/SPEKTRUM.2021.v08.i01.p29.