Analisis Pengaruh Harmonisa Terhadap Rugi-Rugi Daya (Losses) Pada Transformator di Penyulang Sedap Malam

  • I Gede Ariana Udayana University
  • I G Dyana Arjana Teknik Elektro Unud
  • I Wayan Rinas Teknik Elektro Unud

Abstract

Abstract?The aim of this study is to analyze the influence of harmonic to power losses in transformator atSedapMalam feeder by using the help of ETAP power station, so we can obtain how .
much the influence of harmonic in distribution system. By measuring THDv and THDi in DT0042, DT0048 and DT0319 transformator we got THDv value of 1.1% in DT0042, 1.56% in DT 48 and 1.23% in DT0319 from maximum margin of 5.0% in THDV according to IEEE 519–1992 standard. As for THDi we got the
value of 9.36% in DT0042, 12.4% in DT0048 and 14.2% in DT0319 from maximum margin of 8.0% in THDi according to IEEE 519 –1992 standard. On other side, the result by running ETAP power station we got THDi value of 1.59% in D00T42, 1.95% in DT0048 and 1.71% in DT0319. As for THDv we got running result of 12.22%
in DT0042, 12.96% in DT0048 and 13.54% in DT0319. Based on the result of performed analisis of the influence of harmonic to power losses in transformator at SedapMalam feeder, we obtained that the amount of power losses was 43,2 kW before having harmonic and 45,7 kW after having harmonic. The raise of 2,5 kW was caused by occurance of harmonic in DT0042, DT0048 and DT0319 transformator from total of 44 existed transformators Keywords :Distribution, Harmonic,THDv,THDi, Power Losses.

Downloads

Download data is not yet available.

Author Biographies

I Gede Ariana, Udayana University
Teknik Elektro UNUD
I G Dyana Arjana, Teknik Elektro Unud
Teknik Elektro Unud
I Wayan Rinas, Teknik Elektro Unud
Teknik Elektro Unud

References

[1] Setiawan, A. 2007. Kajian Pengaruh Harmonisa Terhadap Sistem Tenaga Listrik. Jurnal Eltek ISSN 1693-4024 Volume 05 Nomor 02, Oktober 2007
[2] Suweden, Rinas. 2009. Analisa Penanggulangan Thd Dengan Filter Pasif Pada Sistem Kelistrikan Di Rsup Sanglah. Jurnal Teknologi Elektro, Vol. 8 No.2 Juli - Desember 2009
[3] Duffey, C.K. 1989. Update of Harmonic Standard IEEE-51. IEEE Transaction on Industry Application, Vol.25. No.6, November 1989.
[4] Rinas, I Wayan, 2012. Studi Analisis Losses dan Derating Akibat Pengaruh THD Pada Gardu Transformator Daya Di Fakultas Teknik Universitas Udayana. Jurnal Teknologi Elektro, Vol. 11 No. 1 Januari - Juni 2012
[5] Rinas, I Wayan, 2013. Simulasi Penggunaan Filter Pasif, Filter Aktif dan Filter Hybrid Shunt untuk Meredam Meningkatnya Distorsi Harmonisa yang Disebabkan Oleh Munculnya Gangguan Resonansi. Jurnal Teknologi Elektro, Vol. 12 No. 2 Juli- Desember 2013
Published
2016-08-23
How to Cite
ARIANA, I Gede; ARJANA, I G Dyana; RINAS, I Wayan. Analisis Pengaruh Harmonisa Terhadap Rugi-Rugi Daya (Losses) Pada Transformator di Penyulang Sedap Malam. Majalah Ilmiah Teknologi Elektro, [S.l.], v. 16, n. 1, p. 97-106, aug. 2016. ISSN 2503-2372. Available at: <https://ojs.unud.ac.id/index.php/jte/article/view/22113>. Date accessed: 20 apr. 2024. doi: https://doi.org/10.24843/MITE.1601.14.

Keywords

Distribusi, Harmonisa, THDv,THDi, Rugi Daya